Triple IR Optical Detector

Fire Detection Triple IR Optical Detector TRIPLE IR / FLAME DETECTION

Triple IR Optical Detector

Ultra-fast fire detection is critical where explosive threats, flammable materials or high-energy impacts can create a fireball within milliseconds. The Triple IR Optical Detector evaluates three infrared wavelength bands to deliver rapid flame recognition while rejecting common non-fire radiation sources in demanding military, industrial and energy-sector environments.

Detection Speed < 3 ms
IR Channels 3 Wavelength Bands
Detection Range > 60 m
Protection Level IP67

A multi-spectrum infrared flame detector developed for applications where fast fireball recognition and strong resistance to false alarms are essential to the protection strategy.

Three-Band Infrared Detection for Rapid Fire Events

Fireballs produced by fuel ignition, explosive threats or high-energy impacts can develop before conventional heat or smoke detection has time to respond. Triple IR technology addresses this challenge by evaluating flame-related radiation across three independent infrared wavelength bands.

The Triple IR Optical Detector is specified to detect the fireball associated with armor penetration within 3 milliseconds. An alarm is generated when the detector's three IR channels confirm the required flame signature, supporting rapid signaling to the connected control and suppression architecture.

01 / DETECTION

Multi-Wavelength Confirmation with Advanced Signal Processing

The detector monitors IR1 at 4.5–5.5 μm, IR2 at 3.0–3.6 μm and IR3 at 0.8–1.2 μm. By comparing these separate infrared regions, the system can evaluate whether the observed radiation pattern is consistent with a genuine flame event.

The source documentation identifies ultra-fast semiconductor IR quantum sensors, two high-performance microprocessors and advanced software algorithms as part of the detection architecture. Requiring confirmation across all three IR channels helps reduce unwanted alarms from non-fire radiation sources.

Triple-Band
Detection
3 IR
Bands

Fast Response with False-Alarm Rejection

Triple-band confirmation is used to separate real flame signatures from common optical and thermal interference. The supplied source specifically identifies immunity to sunlight and solar fluctuations, vehicle headlights, welding arcs, infrared heaters and cigarette ash.

The detector is also described as suitable for harsh environments, with IP67 protection. The source states that this level allows the detector to remain submerged under 1 meter of water for up to 30 minutes.

Detection Performance

Triple IR Optical Detector Highlights

01

Sub-3 ms Fireball Detection

The product source specifies detection of an armor-penetration fireball within 3 milliseconds.

02

Three IR Wavelength Bands

IR1, IR2 and IR3 channels evaluate flame radiation across three separate infrared spectral regions.

03

Strong False-Alarm Immunity

Three-channel confirmation helps reject non-fire sources such as sunlight, headlights, welding arcs and infrared heaters.

04

Long-Range Detection

The supplied source lists a detection range exceeding 60 meters when the detector operates in high-sensitivity mode.

05

Multiple Interfaces

Communication options listed in the source include ModBus RS-485, analog output and relay interfaces.

06

Visual Status Indication

Green indicates energized status, red indicates alarm and yellow identifies a fault or error condition.

Detection Architecture

Triple IR Detection Architecture

CHANNEL / IR1

IR1 Detection Band

Wavelength
4.5–5.5 μm.
Role
One of three independent infrared channels used for flame-signature confirmation.
Processing
Evaluated together with IR2 and IR3 before alarm confirmation.
CHANNEL / IR2

IR2 Detection Band

Wavelength
3.0–3.6 μm.
Role
Provides a second spectral reference for differentiating flame radiation from interference.
Processing
Part of the detector's three-band confirmation logic.
CHANNEL / IR3

IR3 Detection Band

Wavelength
0.8–1.2 μm.
Role
Completes the three-channel infrared comparison used for flame recognition.
Processing
Alarm generation requires confirmation across all three IR sensors.
Operational Use

Application Areas

Armored & Military Vehicles
Oil Refineries & Petrochemical Plants
Offshore Platforms & Pipelines
LNG / LPG Transfer Areas
Marine & Aviation Platforms
Fuel, Solvent & Industrial Storage Areas
Qualification

Testing Standards & Certification References

The supplied product content identifies NATO STANAG 4317 and MIL-PRF-62546C for the detector's military fire-detection context. It also lists EN 54-22, UL 268, FM Approval Standards and ISO 7240-24 under testing standards, together with FM approval, ATEX certification, CE marking and SIL 2 compatibility.

NATO STANAG 4317
MIL-PRF-62546C
EN 54-22
UL 268
FM Approval Standards
ISO 7240-24
ATEX / CE
SIL 2 Compatible
FAQ / PRODUCT

Frequently Asked Questions

01 Which infrared wavelength bands are monitored by the Triple IR Optical Detector?

The detector monitors IR1 at 4.5–5.5 μm, IR2 at 3.0–3.6 μm and IR3 at 0.8–1.2 μm.

02 How is a flame alarm confirmed across the detector's three IR channels?

The supplied product content states that an alarm is generated only when all three IR sensors simultaneously confirm a flame signature.

03 Which communication interfaces are listed for system integration?

The source lists ModBus RS-485, analog output and relay interfaces.

04 What do the detector's visual status indicators represent?

Green indicates energized status, red indicates alarm and yellow indicates a fault or error condition.

05 Which fire types are identified in the source as suitable detection targets?

The source identifies hydrocarbon fires involving petrol, methane, diesel and LPG, as well as paper, wood and solvent fires.

Product Specifications

Technical Data

Test Performed Headlight (55–65 W)
Spec Requirement 15 cm
Test Performed Incandescent Lamp (100 W)
Spec Requirement 2.5 cm
Test Performed Halogen Lamp (500 W)
Spec Requirement 5 cm
Test Performed Fluorescent Light (40 W)
Spec Requirement At Any Distance
Test Performed UV Lamp (75 W)
Spec Requirement At Any Distance
Test Performed In-Vehicle Lighting (5 W)
Spec Requirement At Any Distance
Test Performed Match
Spec Requirement 20 cm
Test Performed Sodium Lamp (70–250 W)
Spec Requirement At Any Distance
Test Performed Xenon Lamp (30 W)
Spec Requirement 5 cm
Test Performed Flashlight (1 W)
Spec Requirement At Any Distance
Fire Bulgaria / Product Support

Need More Information About This System?

Contact our team for detector specifications, integration requirements and application-specific fire detection configurations.

Request Information